Kidde Smoke Alarm PI2000CA User Manual

120 V AC and 9 V Battery Backup  
Dual Sensor  
Smoke Alarm  
®
Photoelectric / Ionization with Hush Control Feature  
Alarm Manual  
Model PI2000CA  
Ionization sensing alarms may detect invisible fire  
particles (associated with fast flaming fires) sooner  
SINGLE AND/ OR  
MULTIPLE STATION  
SMOKE ALARM  
than photoelectric alarms. Photoelectric sensing  
alarms may detect visible fire particles (associated  
with slow smoldering fires) sooner than ionization  
alarms. Home fires develop in different ways and  
are often unpredictable. For maximum protection,  
Kidde recommends that both Ionization and  
Photoelectric alarms be installed.  
Download from Www.Somanuals.com. All Manuals Search And Download  
Installation  
This unit is suitable as a single station and/or multiple  
station alarm (interconnects with up to 24 devices), and  
has a five-year limited warranty.  
IMPORTANT:This unit is only approved to interconnect  
with the Kidde line of products. It is not approved to  
interconnect with any other manufacturer’s products.  
This alarm is interconnect compatible with the following  
alarms and accessories:  
Smoke alarms:  
1235CA, 1275CA, 1276CA, 1285CA,  
i12020CA, i12040CA, i12060CA,  
PE120CA, PI2000CA  
Smoke/CO alarms: KN-COSM-IBCA, KN-COSM-ICA  
CO alarms:  
Relay modules:  
Heat alarm:  
Strobe Light:  
KN-COB-ICB-CA, KN-COB-IC-CA  
120X, SM120X, CO120X  
HD135FCA  
SL177I  
Refer to respective manuals for specific application  
information.  
This product is designed to detect products of combustion  
using both an ionization sensor and a photoelectric sensor.  
The ionization sensor contains 0.9 microcurie of Americium  
241, a radioactive material. Distributed under U.S. NRC  
License No. 32-23858-01E. Manufactured in compliance  
with U.S. NRC safety criteria in 10 CFR 32.27. The  
purchaser is exempt from any regulatory requirements. Do  
not try to repair the smoke alarm yourself. Refer to the  
instructions in Warranty for service.  
ELECTRICAL RATING: 120 V AC, 60 HZ, 80 mA maximum  
per alarm (maximum 80 mA for originating unit with 24  
devices interconnected).  
WARNING! Battery door will not close unless battery is present.  
Removal of the smoke alarm battery and disconnecting or loss of  
A.C power will render the smoke alarm inoperative.  
IMPORTANT! Read all instructions before installation and keep  
this manual near the alarm for future reference.  
Download from Www.Somanuals.com. All Manuals Search And Download  
2
Installation  
Recommended Locations  
• Locate the first alarm in the immediate area of the  
bedrooms. Try to monitor the exit path, as the  
bedrooms are usually farthest from the exit. If more  
than one sleeping area exists, locate additional alarms in  
each sleeping area (Image 1A).  
• Locate additional alarms to monitor any stairway as  
stairways act like chimneys for smoke and heat.  
• Locate at least one alarm on every floor level (Image 1B).  
• Locate an alarm in every bedroom.  
• Locate an alarm in every room where electrical  
appliances are operated (i.e. portable heaters or  
humidifiers).  
• Locate an alarm in every room where someone sleeps  
with the door closed. The closed door may prevent an  
alarm not located in that room from waking the sleeper.  
• Smoke, heat, and combustion products rise to the  
ceiling and spread horizontally. Mounting the smoke  
alarm on the ceiling in the centre of the room places it  
closest to all points in the room. Ceiling mounting is  
preferred in ordinary residential construction.  
• When mounting an alarm on the ceiling, locate it at a  
minimum of 10 cm (4") from the side wall (Image 2A).  
• When mounting the alarm on the wall, use an inside  
wall with the top edge of the alarm at a minimum of 10  
cm (4") and a maximum of 30.5 cm (12") below the  
ceiling (Image 2A).  
• Put smoke alarms at both ends of a bedroom hallway  
or large room if the hallway or room is more than 9.1 m  
(30') long.  
• For mobile home installation, select locations carefully  
to avoid thermal barriers that may form at the ceiling.  
For more details, see Mobile Homes.  
Download from Www.Somanuals.com. All Manuals Search And Download  
3
Installation  
DINING  
ROOM  
KITCHEN  
BEDROOM BEDROOM  
BEDROOM  
HALL  
BEDROOM  
KITCHEN  
LIVING  
ROOM  
BEDROOM  
LIVING  
ROOM  
Smoke Alarms for Minimum Protection  
Smoke Alarms for Additional Protection  
BASEMENT  
Ionization Type Smoke Alarm with  
Hush® or Photoelectric Type  
SINGLE FLOOR PLAN  
MULTIPLE FLOOR PLAN  
IMAGE 1A  
IMAGE 1B  
• Install smoke alarms on sloped, peaked or cathedral  
ceilings at or within 0.9 m (3') of the highest point  
(measured horizontally). NFPA Standard 72 states: “Smoke  
alarms in rooms with ceiling slopes greater than 0.3 m in  
2.4 m (1' in 8') horizontally shall be located on the high  
side of the room.” NFPA Standard 72 states: “A row of  
detectors shall be spaced and located within 0.9 m (3') of  
the peak of the ceiling measured horizontally” (Image 2B  
and Image 2C).  
BEDROOM  
HALL  
MASTER  
BEDROOM  
FIRE  
EXTINGUISHERS  
SMOKE  
ALARMS  
KITCHEN  
FAMILY ROOM  
GARAGE  
CARBON  
MONOXIDE  
ALARMS  
BASEMENT  
WORKSHOP  
TALKING  
SMOKE/CO  
ALARM  
IMAGE 1C  
TOTAL HOME PROTECTION  
Download from Www.Somanuals.com. All Manuals Search And Download  
4
Installation  
Locations to Avoid  
• Do not install within 0.9 m (3') of the following: The  
door to a kitchen, or a bathroom that contains a tub or  
shower, forced air supply ducts used for heating or  
cooling, ceiling or whole house ventilating fans, or  
other high, air-flow areas.  
• Do not place the alarm where drapes or other objects  
will block the sensor. Smoke must be able to reach the  
sensor to accurately detect conditions.  
• Do not install in peaks of vaulted ceilings, “A” frame  
ceilings or gabled roofs. (Less than 10 cm (4") from the  
peak of an “A” frame type ceiling.)  
• Install at least 30.5 cm (12") away from fluorescent  
lights as electronic noise may cause nuisance alarms.  
• Keep out of insect infested areas. Avoid excessively  
dusty, dirty or greasy areas. Dust particles may cause  
nuisance alarms or failure to alarm.  
• Extreme temperatures may effect the sensitivity of the  
alarm. Do not install in areas where the temperature is  
colder than 4.4°C (40°F) or hotter than 37.8°C (100°F),  
such as garages or unfinished attics.  
• Do not install in areas where the relative humidity (RH)  
is greater than 85%. Very humid areas, with moisture or  
steam, can cause nuisance alarms.  
• Avoid placing ionization smoke alarms in kitchen areas.  
Normal cooking may cause nuisance alarms. If a  
®
kitchen alarm is desired, it should have Hush control  
feature or be a photoelectric type.  
• Do not place in the garage. Particles of combustion are  
present when you start your automobile.  
• Smoke alarms are not to be used with detector guards  
unless the combination (alarm and guard) has been  
evaluated and found suitable for that purpose.  
Download from Www.Somanuals.com. All Manuals Search And Download  
5
Installation  
10 cm (4”)  
MINIMUM  
CEILING  
IMAGE 2A  
NEVER HERE  
BEST  
PLACEMENT  
ACCEPTABLE  
PLACEMENT  
SIDE WALL  
NOT IN  
THIS AREA  
IMAGE 2B  
10 cm (4”)  
ANYWHERE IN THIS  
AREA  
0.9 m (3’)  
0.9 m (3’)  
HORIZONTAL DISTANCE FROM PEAK  
IMAGE 2C  
NOT IN  
THIS AREA  
ANYWHERE IN THIS  
AREA  
10 cm (4”)  
0.9 m (3’)  
Download from Www.Somanuals.com. All Manuals Search And Download  
6
Installation  
Mobile Homes  
Modern mobile homes have been designed to be energy efficient.  
Install smoke alarms as recommended in Recommended Locations and  
Image 2A.  
In older mobile homes that are not well-insulated compared to  
present standards, extreme heat or cold can be transferred from the  
outside to the inside through poorly insulated walls and roof. This  
may create a thermal barrier that can prevent the smoke from  
reaching an alarm mounted on the ceiling. In such units, install the  
smoke alarm on an inside wall with the top edge of the alarm at a  
minimum of 10 cm (4") and a maximum of 30.5 cm (12") below the  
ceiling (Image 2A).  
If you are not sure about the insulation in your mobile home, or if  
you notice that the outer walls and ceiling are either hot or cold,  
install the alarm on an inside wall. For minimum protection, install at  
least one alarm close to the bedrooms. For additional protection, see  
Image 1A.  
WARNING: Test your smoke alarm operation after R.V. or mobile home vehicle  
has been in storage, before each trip and at least once a week during use.  
Wiring Requirements  
• This smoke alarm should be installed on a CSA listed or recognized  
junction box. All connections should be made by a qualified  
electrician and all wiring used shall be in accordance with articles  
210 and 300.3(B) of the U.S. National Electrical Code ANSI/NFPA  
70, NFPA 72 and/or any other codes having jurisdiction in your  
area. The multiple station interconnect wiring must be run in the  
same raceway or cable as the AC power wiring to the alarms. In  
addition, the resistance of the interconnect wiring shall be a  
maximum of 10 ohms.  
• The appropriate power source is 120 Volt AC Single Phase supplied  
from a non-switchable circuit which is not protected by a ground  
fault interrupter.  
WARNING: The alarm should not be operated on power derived  
from a square wave, modified square wave or modified sine wave  
inverter. These power sources produce high peak voltages that will  
damage the alarm. These types of inverters are sometimes used to  
supply power to the structure in off grid installations, such as solar  
or wind derived power sources.  
Download from Www.Somanuals.com. All Manuals Search And Download  
7
Installation  
Wiring Instructions  
CAUTION! Turn off the main power to the circuit before wiring  
the alarm.  
• For alarms that are used as single station, DO NOT CONNECT  
THE RED WIRE TO ANYTHING. Leave the red wire insulating  
cap in place to make certain that the red wire cannot contact  
any metal parts or the electrical box.  
• When alarms are interconnected, all interconnected units must  
be powered from a single circuit.  
• A maximum of 24 Kidde devices may be interconnected in a  
multiple station arrangement. The interconnect system should  
not exceed the NFPA interconnect limit of 12 smoke alarms  
and/or 18 alarms total (smoke, heat, carbon monoxide, etc.)  
With 18 alarms interconnected, it is still possible to interconnect  
up to a total of 6 remote signaling devices and/or relay modules.  
CAUTION! Kidde alarm and accessories CAN ONLY BE  
interconnected with other Kidde alarms and accessories as well  
as specified brands and models of interconnect compatible alarms.  
Connection of Kidde products to a non-specified manufacturer’s  
interconnect system, or connection with non-specified equipment  
from another manufacturer into an existing Kidde system could  
result in nuisance alarming, failure to alarm, or damage to one  
or all of the devices in the interconnect system. Refer to the  
User’s Guide supplied with each Kidde product for interconnect  
compatible models, brands, and devices.  
• When mixing models which have battery backup with models  
without battery backup, be advised that the models without  
battery backup will not respond during an AC power failure.  
• The maximum wire run distance between the first and last  
unit in an interconnected system is 305 m (1000').  
• Image 3 illustrates interconnection wiring. Improper connection  
will result in damage to the alarm, failure to operate, or a  
shock hazard.  
• Make certain alarms are wired to a continuous (non-switched)  
power line. NOTE: Use standard CSA listed household wire  
(as required by local codes) available at all electrical supply  
stores and most hardware stores.  
Download from Www.Somanuals.com. All Manuals Search And Download  
8
Installation  
IMAGE 3  
INTERCONNECT WIRING  
Download from Www.Somanuals.com. All Manuals Search And Download  
9
Installation  
Mounting  
CAUTION: This unit is sealed. The cover is not removable!  
• Remove the mounting plate from the back of the alarm by  
holding the mounting plate and twisting the alarm in the  
direction indicated by the “OFF” arrow on the alarm cover.  
• After selecting the proper smoke alarm location as described  
previously, and wiring the AC Quick-Connect wire harness as  
described in Wiring Instructions, attach the mounting plate to  
the electrical box (Image 4B).  
A
A
“A” LINE  
ALIGNMENT MARKS  
IMAGE 4A  
IMAGE 4B  
Remove  
Install  
WALL MOUNTING  
POSITION  
ROTATE TO MOUNT OR  
TO REMOVE  
IMAGE 4C  
IMAGE 4D  
Download from Www.Somanuals.com. All Manuals Search And Download  
10  
Installation  
• Pull the AC Quick-Connect wire harness through the  
center hole in the mounting bracket and secure the  
bracket, making sure that the mounting screws are  
positioned in the small ends of the keyholes before  
tightening.  
• Plug the AC Quick-Connect wire harness into the back  
of the alarm (Image 5), making sure that the locks on  
the connector snap into place. Then push the excess  
wire back into the electrical box through the hole in the  
center of the mounting plate.  
• Install the alarm on the mounting plate and rotate the  
alarm in the direction of the “ON” arrow on the cover  
until the alarm ratchets into place (Image 4D). This  
ratcheting function allows for aesthetic alignment. Note:  
The alarm will attach to the mounting plate in 4  
positions (every 90°).  
• Turn on the AC power. The green AC Power On indicator  
should be lit when the alarm is operating from AC power.  
IMAGE 5  
ATTACHING THE AC QUICK-CONNECT WIRE HARNESS  
Download from Www.Somanuals.com. All Manuals Search And Download  
11  
Installation  
Battery  
This unit will not function without a properly installed  
battery. When installing a battery, press the battery  
reminder tab down into the battery compartment and  
install the battery (See Image 6A and 6B). For initial  
installation a pre-installed 9 V battery is included with a  
battery pull tab that allows for easy connection.  
CAUTION: If the battery reminder tab is not held down in the  
battery compartment by the battery, the battery door will not  
close and the unit will not attach to the mounting plate.  
Battery  
tab  
IMAGE 6A  
IMAGE 6B  
Testing  
• After installation, test your alarm by depressing and  
holding down the test button for 5 seconds or until the  
alarm sounds.  
CAUTION: Due to the loudness (85 decibels) of the alarm, always  
stand an arms-length away from the unit when testing.  
Operation  
The smoke alarm is operating once a fresh battery is installed  
and testing is complete. When the smoke alarm ionization  
sensor chamber senses products of combustion, the horn will  
sound a loud (85 db) alarm until the sensing chamber is  
cleared of smoke particles.  
Download from Www.Somanuals.com. All Manuals Search And Dow1nl2oad  
Operation  
®
Hush Control Feature  
Smoke alarms are designed to minimize nuisance alarms.  
Cigarette smoke will not normally set off the alarm, unless  
the smoke is blown directly into the alarm. Combustion  
particles from cooking may set off the alarm if the alarm is  
located close to the cooking area. Large quantities of  
combustible particles are generated from spills or when  
broiling. Using the fan on a range hood that vents to the  
outside (non-recirculating type) will also help remove  
®
these combustible particles from the kitchen. The Hush  
button is extremely useful in a kitchen area or other areas  
prone to nuisance alarms.  
®
The Hush feature has the capability of temporarily  
desensitizing the smoke alarm circuit for about 8 minutes.  
This feature is to be used only when a known alarm  
condition, such as smoke from cooking, activates the alarm.  
If the alarm does sound, check for fires first. If a fire is  
discovered, get out and call the fire department. If no fire  
is present, check to see if one of the reasons listed in  
Locations to Avoid may have caused the alarm.  
®
The smoke alarm is desensitized by pushing the Hush  
button on the smoke alarm cover. If the smoke is not too  
dense, the alarm will silence immediately and the red LED  
will flash every 2 seconds for approximately 8 minutes. This  
indicates that the alarm is in a temporarily desensitized  
condition. The smoke alarm will automatically reset after  
approximately 8 minutes. If after this period particles of  
combustion are still present, the alarm will sound again.  
®
The Hush feature can be used repeatedly until the air has  
been cleared of the condition causing the alarm. Pushing  
the Test button on the alarm will end the alarm silencing  
period.  
NOTE: Dense smoke will override the Hush® feature and sound a  
continuous alarm.  
CAUTION: Before using the Hush® feature, identify the source of  
the smoke and be certain a safe condition exists.  
Do1w3nload from Www.Somanuals.com. All Manuals Search And Download  
Operation  
Alarm Tamper-Resist Feature  
This alarm has a tamper-resist feature. This feature will  
help deter children or others from removing the alarm  
from the mounting plate.  
Activate the tamper-resist feature by breaking off the four  
posts in the square holes in the mounting plate (see Image 7A).  
Rotate the alarm onto the mounting plate until you hear  
the tamper-resist tab snap into place, locking the alarm. To  
remove the alarm, press on the tamper resist tab and  
rotate the alarm off the mounting plate.  
LOCATION  
OF POSTS  
A
A
IMAGE 7A  
IMAGE 7B  
IMAGE 7C  
IMAGE 7D  
Download from Www.Somanuals.com. All Manuals Search And Download  
14  
Operation  
LED Indicators  
This smoke alarm is equipped with red and green LED  
indicators. The red LED is located under the test button and  
has several modes of operation. The green LED is located  
®
under the Hush button and indicates the presence of AC  
power.  
Standby Condition  
The red LED will flash every 30–40  
seconds to indicate that the smoke  
alarm is operating properly. The green  
LED will be lit, indicating the presence  
of AC power.  
Alarm Condition  
When the alarm senses particles of  
combustion and goes into alarm, the  
red LED will flash rapidly (once every  
two seconds). The rapid flashing LED  
and temporal alarm will continue  
until the air is cleared.  
Hush Condition  
The red LED will flash every 2 seconds  
®
as long as the alarm is in Hush mode.  
Low Battery Condition The red LED flash will be accompanied  
by an audible chirp. Replace the  
battery when this condition occurs.  
Alarm Memory  
This smoke alarm is equipped with  
an alarm memory which provides a  
visual indication when an alarm has  
been activated. A lit red LED  
indicates the memory condition. The  
memory will remain activated until it  
is reset by pushing the test button.  
Smoke Sensing Chamber Operation  
The alarm will “chirp” if any of the components in the smoke  
sensing chamber fail. This chirp will occur between the  
flashes of the red LED indicator light. If the “chirp” occurs at  
the same time as the red LED flash, see Battery Replacement  
section for more information.  
Do1w5nload from Www.Somanuals.com. All Manuals Search And Download  
Operation  
When Units Are Interconnected  
Only the red LED of the alarm “which senses the smoke” or  
“is being tested” (the originating unit) will flash rapidly. All  
other units in the interconnect system will sound an alarm  
but their red LED’s will NOT flash rapidly.  
Testing  
Test by pushing the Test button on the cover and hold  
it down for a minimum of 5 seconds. This will sound  
the alarm if all the electronic circuitry, horn and battery  
are working. In an interconnected installation all  
interconnected alarms should sound when the test button  
on any one of the interconnected alarms is pressed. If  
no alarm sounds, the unit has defective batteries or other  
failure. DO NOT use an open flame to test your alarm,  
you could damage the alarm or ignite combustible  
materials and start a structure fire.  
Alarm Memory  
This smoke alarm is equipped with an alarm memory  
feature which produces a visual indication when an alarm  
has been activated. A lit red LED indicates the memory  
condition. The memory will remain activated until it is  
reset by pushing the test button.  
Test the alarm weekly to ensure proper operation. Erratic  
or low sound coming from your alarm may indicate a  
defective alarm, and it should be returned to place of  
purchase (see Warranty section).  
NOTE: WEEKLY TESTING IS REQUIRED!  
Download from Www.Somanuals.com. All Manuals Search And Download  
16  
Maintenance  
Alarm Removal  
If the smoke alarm tamper resist feature has been activated, refer  
to the alarm tamper-resist feature section for removal instructions.  
To remove the alarm from the mounting plate, rotate the alarm  
in the direction of the “OFF” arrow on the cover. To  
disconnect the AC power harness, squeeze the locking arms  
on the sides of the Quick Connector while pulling the  
connector away from the bottom of the alarm.  
Battery Replacement  
To replace or install the batteries you must first remove the  
alarm from the mounting plate by following the ALARM  
REMOVAL instructions at the beginning of this section. After the  
alarm has been removed, you can open the battery door and  
install or replace the battery. Battery installation instructions are  
provided on the inside of the battery door.  
This smoke alarm uses a 9 V alkaline battery (a lithium battery  
may also be used). A fresh alkaline battery should last for one  
year under normal operating conditions. This alarm has a low  
battery monitor circuit which will cause the alarm to “chirp”  
approximately every 30 seconds for a minimum of 7 days when  
the battery loses power. Replace when this condition occurs.  
Use only the following 9 V batteries for replacement:  
Alkaline Type  
Energizer 522  
Duracell MN1604 or MX1604  
Gold Peak 1604A  
Panasonic 6AM6, 6AM-6, 6AM-6PI,  
6AM6X, and 6LR61(GA)  
Ultralife U9VL-J  
Lithium Type  
After installing or changing the battery, reinstall your alarm.Test  
your alarm by using the test button and check that the green  
LED is on.  
Do1w7nload from Www.Somanuals.com. All Manuals Search And Download  
Maintenance  
WARNING! Use only the batteries specified. Use of different batteries  
than the recommended ones, may have a detrimental effect on the  
smoke alarm. A good safety measure is to replace the battery at least  
once a year, or at the same time you change your clocks for daylight  
saving time. Be sure to follow the battery installation instructions  
printed on the back of the alarm.  
NOTE: WEEKLY TESTING IS REQUIRED!  
NOTE: If after battery replacement the alarm continues to chirp,  
®
push the Test button. The Hush feature may have been  
activated accidently while changing the battery and pushing the  
®
Test button will end the Hush cycle.  
Cleaning the Alarm  
The alarm should be cleaned at least once a year.  
• To clean your alarm, remove it from the mounting plate as  
outlined in previous sections. You can clean the alarm by  
using compressed air or a vacuum cleaner hose with a soft  
brush attachment. Blow or vacuum around the perimeter of  
the alarm to remove dust and dirt. The outside of the alarm  
can be wiped with a damp cloth (do not use a wet cloth to  
avoid water entering the unit).  
• After cleaning, reinstall your alarm and test your alarm by  
using the Test button. If cleaning does not restore the alarm  
to normal operation, the alarm should be replaced.  
• Do not paint the unit. Paint will seal the vents and interfere  
with the sensor’s ability to detect smoke. Never attempt to  
disassemble the unit or clean inside. This action will void  
your warranty.  
Replacing the Alarm  
The National Fire Protection Association (NFPA) recommend  
replacing this alarm ten years from the date code label (located  
on the back of the alarm).  
Download from Www.Somanuals.com. All Manuals Search And Download  
18  
Fire Safety  
Limitations of Smoke Alarms  
WARNING: Please read carefully and thoroughly.  
• NFPA 72 states: Life safety from fire in residential occupancies  
is based primarily on early notification to occupants of the  
need to escape, followed by the appropriate egress actions  
by those occupants. Fire warning systems for dwelling units  
are capable of protecting about half of the occupants in  
potentially fatal fires. Victims are often intimate with the  
fire, too old or young, or physically or mentally impaired  
such that they cannot escape even when warned early  
enough that escape should be possible. For these people,  
other strategies such as protection-in-place or assisted  
escape or rescue are necessary.  
• Smoke alarms are devices that can provide early  
warning of possible fires at a reasonable cost; however,  
alarms have sensing limitations. Ionization sensing  
alarms may detect invisible fire particles (associated  
with fast flaming fires) sooner than photoelectric alarms.  
Photoelectric sensing alarms may detect visible fire  
particles (associated with slow, smouldering fires)  
sooner than ionization alarms. Home fires develop in  
different ways and are often unpredictable. For  
maximum protection, Kidde recommends that both  
ionization and photoelectric alarms be installed.  
• A battery powered alarm must have a battery of the  
specified type, in good condition and installed properly.  
• AC powered alarms (without battery backup) will not  
operate if the AC power has been cut off, such as by an  
electrical fire or an open fuse.  
• Smoke alarms must be tested regularly to make sure the  
batteries and the alarm circuits are in good operating  
condition.  
• Smoke alarms cannot provide an alarm if smoke does  
not reach the alarm. Therefore, smoke alarms may not  
sense fires starting in chimneys, walls, on roofs, on the  
other side of a closed door or on a different floor.  
• If the alarm is located outside the bedroom or on a  
different floor, it may not wake up a sound sleeper.  
Do1w9nload from Www.Somanuals.com. All Manuals Search And Download  
Fire Safety  
• The use of alcohol or drugs may also impair one’s  
ability to hear the smoke alarm. For maximum  
protection, a smoke alarm should be installed in each  
sleeping area on every level of a home.  
• Although smoke alarms can help save lives by providing  
an early warning of a fire, they are not a substitute for  
an insurance policy. Home owners and renters should  
have adequate insurance to protect their lives and property.  
Good Safety Habits  
Develop and practice a plan of escape!  
• Make a floor plan indicating all doors and windows and  
at least two (2) escape routes from each room. Second  
story windows may need an escape ladder.  
• Have a family meeting and discuss your escape plan,  
showing everyone what to do in case of fire.  
• Determine a place outside your home where you all  
can meet if a fire occurs.  
• Familiarize everyone with the sound of the smoke alarm  
and train them to leave your home when they hear it.  
• Practice a fire drill at least every six months, including  
fire drills at night. Ensure that small children hear the  
alarm and wake when it sounds. They must wake up in  
order to execute the escape plan. Practice allows all  
occupants to test your plan before an emergency. You  
may not be able to reach your children. It is important  
they know what to do.  
• Install and maintain fire extinguishers on every level of the  
home and in the kitchen, basement and garage. Know  
how to use a fire extinguisher prior to an emergency.  
• Current studies have shown smoke alarms may not  
awaken all sleeping individuals, and that it is the  
responsibility of individuals in the household that are  
capable of assisting others to provide assistance to those  
who may not be awakened by the alarm sound, or to  
those who may be incapable of safely evacuating the  
area unassisted.  
Download from Www.Somanuals.com. All Manuals Search And Download  
20  
Fire Safety  
What To Do When The Alarm Sounds  
• Alert small children in the home.  
• Leave immediately by your escape plan. Every second  
counts, so don’t waste time getting dressed or picking  
up valuables.  
• In leaving, don’t open any inside door without first  
feeling its surface. If hot, or if you see smoke seeping  
through cracks, don’t open that door! Instead, use your  
alternate exit. If the inside of the door is cool, place  
your shoulder against it, open it slightly and be ready to  
slam it shut if heat and smoke rush in.  
• Stay close to the floor if the air is smoky. Breathe  
shallowly through a cloth, wet if possible.  
• Once outside, go to your selected meeting place and  
make sure everyone is there.  
• Call the fire department from your neighbor’s home–not  
from yours!  
• Don’t return to your home until the fire officials say that  
it is all right to do so.  
There are situations where a smoke alarm may not be  
effective to protect against fire as stated in the NFPA  
Standard 72. For instance:  
a) smoking in bed  
b) leaving children home alone  
c) cleaning with flammable liquids, such as gasoline.  
NRC Information  
Ionization type smoke alarms use a very small amount of a  
radioactive element in the sensing chamber to enable detection  
of visible and invisible combustion products. The radioactive  
element is safely contained in the chamber and requires no  
adjustments or maintenance. This smoke alarm meets or  
exceeds all government standards. It is manufactured and  
distributed under license from the U.S. Nuclear Regulatory  
Commission.  
Download from Www.Somanuals.com. All Manuals Search And Download  
21  
Fire Safety  
Additional Recommendations  
The National Fire Protection Association’s Standard 72  
provides the following information:  
Smoke Detection. Where required by applicable laws,  
codes, or standards for the specified occupancy, approved  
single- and multiple-station smoke alarms shall be  
installed as follows: (1) In all sleeping rooms Exception:  
Smoke alarms shall not be required in sleeping rooms in  
existing one- and two-family dwelling units. (2) Outside  
of each separate sleeping area, in immediate vicinity of  
the sleeping rooms. (3) On each level of the dwelling  
unit, including basements Exception: In existing one- and  
two-family dwelling units, approved smoke alarms  
powered by batteries are permitted.  
Smoke Detection:Are More Smoke Alarms Desirable?  
Required number of smoke alarms (as shown in Image 1A  
and Image 1B): The required number of smoke alarms  
might not provide reliable early warning protection for  
those areas separated by a door from the areas protected  
by the required smoke alarms. For this reason, it is  
recommended that the householder consider the use of  
additional smoke alarms for those areas for increased  
protection.  
The additional areas include the basement, bedrooms,  
dining room, furnace room, utility room, and hallways not  
protected by the required smoke alarms. The installation  
of the smoke alarms in the kitchen, attic (finished or  
unfinished), or garage is normally not recommended, as  
these locations occasionally experience conditions that  
can result in improper operation.  
Alarms should be installed in accordance with the  
National Fire Protection Association’s Standard 72 (NFPA,  
Batterymarch Park, Quincy, MA 02269).  
Notify your local fire department and insurance company  
of your smoke alarm installation.  
Download from Www.Somanuals.com. All Manuals Search And Download  
22  
Warranty  
If after reviewing this manual you feel that your smoke alarm  
is defective in any way, do not tamper with the unit. In many  
cases, the quickest way to exchange your alarm is to return it  
to the original place of purchase. Alternatively, you may  
return it for servicing to Kidde. If you have questions, call  
Kidde Customer Service at 1-800-880-6788.  
5 Year Limited Warranty  
Kidde warrants to the original purchaser that the enclosed  
smoke alarm (but not the battery) will be free from defects in  
material and workmanship or design under normal use and  
service for a period of five years from the date of purchase.  
The obligation of Kidde under this warranty is limited to  
repairing or replacing the smoke alarm or any part which we  
find to be defective in material, workmanship or design, free  
of charge to the customer, upon sending the smoke alarm  
with proof of date of purchase, postage and return postage  
prepaid, to Kidde, Customer Service Department, 130 Esna  
Park Drive, Markham, ON L3R 1E3. 1-800-880-6788.  
This warranty shall not apply to the smoke alarm if it has  
been damaged, modified, abused or altered after the date of  
purchase or if it fails to operate due to improper maintenance  
or inadequate AC or DC electrical power.  
The liability of Kidde or any of its parent or subsidiary corporations  
arising from the sale of this smoke alarm or under the terms  
of this limited warranty shall not in any case exceed the cost  
of replacement of this smoke alarm and, in no case, shall Kidde  
or any of its parent or subsidiary corporations be liable for  
consequential loss or damages resulting from the failure of this  
smoke alarm or for breach of this or any other warranty, express  
or implied, even if the loss or damage is caused by the  
company’s negligence or fault.  
Since some provinces do not allow limitations on the duration  
of an implied warranty or do not allow the exclusion or  
limitation of incidental or consequential damages, the above  
limitations or exclusions may not apply to you. While this  
warranty gives you specific legal rights, you may also have  
other rights which vary from province to province.  
Also, Kidde makes no warranty, express or implied, written or  
oral, including that of merchantability or fitness for any particular  
purpose, with respect to the battery.  
The above warranty may not be altered except in writing signed  
by both parties hereto.  
Download from Www.Somanuals.com. All Manuals Search And Download  
23  

Ingersoll Rand Marine Sanitation System 67343 User Manual
Intellinet Network Solutions Network Router 523615 User Manual
Jensen Car Stereo System SMPS 600 User Manual
Jonsered Lawn Mower LT2220 CMA2 User Manual
JVC Stereo Receiver LVT1507 012A User Manual
JVC VCR HR A54U User Manual
Karcher Pressure Washer K 254 M User Manual
Kenwood CD Player W8027 User Manual
Kenwood Stereo Receiver KDC X996 User Manual
Keys Fitness Treadmill TRI 83t User Manual